利雅路燃气燃烧器

范文一:利雅路燃气燃烧器FS20说明书下载

燃气燃烧器

RIELLO40

FS20

TYPE556T1CODE3755613

目录

1.技术参数--------------------------------------------------12.结构说明--------------------------------------------------13.配件------------------------------------------------------24.燃烧器的安装----------------------------------------------25.燃烧范围--------------------------------------------------26.适用锅炉--------------------------------------------------27.燃气压力与燃烧器出力的关系--------------------------------38.燃气供应管路----------------------------------------------39.电极位置--------------------------------------------------410.电路连接图------------------------------------------------411.燃烧器启动时序图------------------------------------------512.风门调节--------------------------------------------------613.燃烧器头调节----------------------------------------------614.燃烧状况检查----------------------------------------------615.离子探针电流----------------------------------------------716.空气压力开关----------------------------------------------7

17.燃烧器启动故障现象及其造成原因----------------------------8

中国燃烧机网www.ranshaoji.net安装、使用以及维护说明书

1.技术参数

燃烧功率

热值燃气要求

(天然气)压力

电源电机电容点火变压器用电总功率

��

���

81-232KW=70,000-200,000Kcal/h8-12kWh/m3=7,000-10,340Kcal/m3

最小20mbar—最大35mbar单相,220V±10%50Hz

230V/1.4A5uF

一级230V/1.8A-二级8kV30/mA

0.25kW

对液化石油气(或城市燃气)需要特别的部件。CE标准,符合

90/396/EEC;PIN63AP6680。EMC符合89/336/EEC。

燃烧器符合IP40,EN60529保护标准。燃气阀门组符合EN676标准。

2.结构说明

1—风门

2—紧固螺钉3—电缆垫圈

4—外壳紧固螺钉5—6孔气路组件插座

6—7孔输入和远程控制插座7—报警灯及复位按钮

注意:电缆垫圈(3)和外壳紧固螺钉(4)必须与阀门组在同一方向。结构尺寸

*可使用加长的燃烧头

3.配件

数量141111

说明七针插头紧固螺钉及螺母

石棉垫片外壳紧固螺钉电缆垫圈铰链

4.燃烧器的安装

将燃烧器上部螺钉(1)打开,使图中(A)与(B)部分分开。

在燃烧器头部(B)安上石棉垫片(3)然后与锅炉(2)紧固连接。

5.燃烧范围

6.适用锅炉

��

实验锅炉:以上工作曲线是用符合DIN4788和EN676标准的锅炉测量的。商用锅炉:如果锅炉是符合EN303标准,且燃烧室尺寸与EN676图表所示相近时,则燃烧器与锅炉应该是匹配的。

如果锅炉不是符合EN303标准或者燃烧室尺寸不符合EN676图表,则燃烧器与锅炉是不匹配的。此时应咨询生产厂家。

7.燃气压力与燃烧器出力的关系

在用热值为10kW/m3(8,570kcal/m3)的燃气、锅炉背压为0mbar时进行检测,燃烧器最大出力时燃烧器头部的压降为7.7mbar

8.

燃气供应管路

1—燃气供应管道2—手动阀3—过滤器4—调压阀

符合EN676标准的气体阀门组:

DUNGS气阀型号MBDLE407B01MBDLE410B01

连接尺寸阀门组燃烧器Rp3/4Rp3/4

Rp3/4Rp3/4

5—燃气压力测点

6—燃气压力开关7—电磁阀

8—电磁阀出口燃气压力检测点

燃气条件可更换的RIELLO气阀型

天然气≤180kW1.DUNGSGF507/1过滤器液化石油气2.DUNGSFRS207/1调压器天然气和液化石3.DUNGSGW50A4压力开关

4.Riello487SE和488SE燃气阀油气

燃气控制阀门组的调节方法可参考有关资料。

9.

电极位置

10.

电路连接图

注意

�����

以上电路中不应将零线与火线混淆连接。导线直径1mm2。应有安全接地。

应确定燃烧器能在锅炉温度报警和火焰离子探针与燃烧器连线(红线)断开时,就停止工作。

安装人员对电路的连接应符合当地的法规要求。

11.燃烧器启动时序图

正常工作过程中,灭火后燃烧器在一秒内锁定;如燃烧器不能自启动,需要按一

下复位按钮,之后燃烧器可以重新启动。

12.风门调节

���

风门(1)是由伺服电机(2)控制,燃烧器电源接通后,首先风门完全打开。

拧松调节螺钉(4),将风门开度(3)调到适当的开度。

当达到合适的风门开度时将螺钉4拧紧。

出厂时,风门设置为3。

13.燃烧器头调节:

拧松螺钉A,移动弯管B到合适位置,再拧紧螺钉A。例如:

燃烧器安装在155kW锅炉上,其热效率为90%,燃烧器输出大约为172KW,按照以下图表,燃烧器燃烧头应设在3的

位置。

此图表一般只在初期设定时参照,在运行时为了改变空气配比情况和燃烧状况,可适当更改此设置。

14.燃烧状况检查:

��

CO2的含量应不超过10%,如果CO2含量太高,将会产生由于不完全燃烧或CO含量过高而引起的危险。

按照EN676标准,CO含量应不超过100mg/kWh(80ppm

15.离子探针电流:

燃烧器控制器所需最小电流为3μA。

一般情况下,离子探针电流会大于3μA。在需要检查时,可以打开离子探针红色连接头,串接入微安电流表。

(如图所示)

16.空气压力开关:

��

空气压力开关应在最后调节,开始

时应设在最低位置。

燃烧器工作在最小出力时,顺时针

加大设置值,直至燃烧器锁定,然后将设定值逆时针旋转减小一格。检查燃烧器是否能稳定工作,如果燃烧器突然停机,应再减小空气压力开关的设定值。

注意:

根据有关标准,如果CO含量超过1%(10000ppm),则必须调节空气量及空气压力开关。(应首先确定CO含量的增加是由于风量

不够而引起的)

中国燃烧机网www.ranshaoji.net

安装、使用以及维护说明书

17.燃烧器启动故障现象及其造成原因原因

离子探针接地不好;离子探针未与火焰接触;

燃烧器启动预吹扫及点离子探针与控制盒连线断开。

火后燃烧器锁定离子探针电流太弱。(

燃气压力开关接近于实际燃气压力

点火气量太小,或管道压力太低

燃烧器有预吹扫,无火焰燃气电磁阀损坏

出现,燃烧器锁定点火棒安装错误或损坏

燃气管道内空气未清扫干净

模拟火焰存在(或炉内有火焰存在)不能通过预吹扫,燃烧器气体压力开关未调整好;风压太低;空气压力锁定开关损坏;燃烧头部损坏;燃烧头设置错误

燃气压力开关设定值太高

温度控制开关接通,但燃燃气未供应

烧器不启动燃气压力开关损坏或接触不好

风门执行器损坏

可能是燃气压力开关的设定值与实际压力太

接近,当燃气阀门开启时,使管道燃气压力下燃烧器连续循环执行吹降,压力保护开关动作,燃烧器停机。当燃气扫和点火但不锁定电磁阀关闭后,管道压力上升,燃烧器又重新

启动。排除方法是重新设定燃气压力开关值。

在检查以上情况后,如果故障依然存在,请检查电路的连接及各电插头是否连接好,包括风门伺服电机、燃烧器电机、气阀连线、点火变压器。如果燃烧器仍然不能工作,请与生产厂家联系。故障

运行失败

燃烧器进入锁定主要有如下原因:—火焰非正常熄灭

—离子探针接地不好

—空气压力开关断开

如果燃气压力开关断开,则燃烧器会停机。

9

范文二:利雅路燃气GS10燃烧器燃烧机下载(3)

燃气燃烧器

RIELLO40

GS10

TYPE554T1CODE3755417

目录

1.技术参数--------------------------------------------------12.结构说明--------------------------------------------------13.配件------------------------------------------------------24.燃烧器的安装----------------------------------------------25.燃烧范围--------------------------------------------------26.适用锅炉--------------------------------------------------27.燃气压力与燃烧器出力的关系--------------------------------38.燃气供应管路----------------------------------------------39.电极位置--------------------------------------------------410.电路连接图------------------------------------------------411.燃烧器启动时序图------------------------------------------512.风门调节--------------------------------------------------613.燃烧器头调节----------------------------------------------614.燃烧状况检查----------------------------------------------615.离子探针电流----------------------------------------------716.空气压力开关----------------------------------------------7

17.燃烧器启动故障现象及其造成原因----------------------------8

1.技术参数

燃烧功率

热值燃气要求

(天然气)压力

电源电机电容点火变压器用电总功率

42-116KW=36,000-100,000Kcal/h8-12kWh/m3=7,000-10,340Kcal/m3

最小20mbar—最大35mbar单相,220V±10%50Hz

220V/0.7A2uF

一级230V/1.8A-二级8kV30/mA

0.13kW

�����

对液化石油气(或城市燃气)需要特别的部件。CE标准,符合90/396/EEC;PIN63AP6680。EMC符合89/336/EEC。

燃烧器符合IP40,EN60529保护标准。燃气阀门组符合EN676标准。

2.结构说明

1—风门

2—紧固螺钉

3—7孔输入和远程控制插座4—6孔气路组件插座5—电缆垫圈

6—外壳紧固螺钉

7—报警灯及复位按钮

注意:电缆垫圈(5)和外壳紧固螺钉(6)必须与阀门组在同一方向。

结构尺寸

*

可使用加长的燃烧头

3.配件

数量141111

说明七针插头紧固螺钉及螺母

石棉垫片外壳紧固螺钉电缆垫圈铰链

4.燃烧器的安装

将燃烧器上部螺钉(1)打开,使图中(A)与(B)部分分开。

在燃烧器头部(B)安上石棉垫片(3)然后与锅炉(2)紧固连接。

5.

燃烧范围

mbar

燃烧室背压

6.适用锅炉

��

实验锅炉:以上工作曲线是用符合DIN4788和EN676标准的锅炉测量的。商用锅炉:如果锅炉是符合EN303标准,且燃烧室尺寸与EN676图表所示相近时,则燃烧器与锅炉应该是匹配的。

如果锅炉不是符合EN303标准或者燃烧室尺寸不符合EN676图表,则燃烧器与锅炉是不匹配的。此时应咨询生产厂家。

7.燃气压力与燃烧器出力的关系

在用热值为10kW/m3(8,570kcal/m3)的燃气、锅炉背压为0mbar时进行检测,燃烧器最大出力时燃烧器头部的压降为5.8mbar

8.燃气供应管路

1—燃气供应管道2—手动阀

3—燃气压力测点4—过滤器

5—燃气压力开关

符合EN676标准的气体阀门组:

DUNGS气阀型号

MBDLE405B01MBDLE407B01

连接尺寸

阀门组燃烧器Rp1/2Rp3/4

Rp3/4Rp3/4

6—安全阀

7—稳压阀8—调节阀

M1管道燃气压力检测点M2进口燃气压力检测点

燃气条件天然气≤80kW液化石油气

天然气和液化石油气

可更换的RIELLO气阀型1.DUNGSGF507/1过滤器2.DUNGSFRS207/1调压器3.DUNGSGW50A4压力开关4.Riello487SE和488SE燃气阀

燃气控制阀门组的调节方法可参考有关资料。

9.

电极位置

10.

电路连接图

注意

�����

以上电路中不应将零线与火线混淆连接。导线直径1mm2。应有安全接地。

应确定燃烧器能在锅炉温度报警和火焰离子探针与燃烧器连线(红线)断开时,就停止工作。

安装人员对电路的连接应符合当地的法规要求。

11.燃烧器启动时序图

正常工作过程中,灭火后燃烧器在一秒内锁定;如燃烧器不能自启动,需要按一

下复位按钮,之后燃烧器可以重新启动。

12.风门调节

���

风门(1)是由伺服电机(2)控制,燃烧器电源接通后,首先风门完全打开。

拧松调节螺钉(4),将风门开度(3)调到适当的开度。

当达到合适的风门开度时将螺钉4拧紧。

出厂时,风门设置为3。

13.燃烧器头调节:

拧松螺钉A,移动弯管B到合适位置,再拧紧螺钉A。例如:

燃烧器安装在81kW锅炉上,其热效率为90%,燃烧器输出大约为90KW,按照以下图表,燃烧器燃烧头应设在3的

位置。

此图表一般只在初期设定时参照,在运行时为了改变空气配比情况和燃烧状况,可适当更改此设置。

14.燃烧状况检查:

��

CO2的含量应不超过10%,如果CO2含量太高,将会产生由于不完全燃烧或CO含量过高而引起的危险。

按照EN676标准,CO含量应不超过100mg/kWh(93ppm)

15.离子探针电流:

燃烧器控制器所需最小电流为3μA。

一般情况下,离子探针电流会大于3μA。在需要检查时,可以打开离子探针红色连接头,串接入微安电流表。

(如图所示)

16.空气压力开关:

��

空气压力开关应在最后调节,开始

时应设在最低位置。

燃烧器工作在最小出力时,顺时针加大设置值,直至燃烧器锁定,然后将设定值逆时针旋转减小一格。检查燃烧器是否能稳定工作,如果燃烧器突然停机,应再减小空气压力开关的设定值。

注意:

根据有关标准,如果CO含量超过1%(10000ppm),则必须调节空气量及空气压力开关。(应首先确定CO

含量的增加是由于风量不够而引起的)

中国燃烧机网www.ranshaoji.net

17.燃烧器启动故障现象及其造成原因

原因

离子探针接地不好;离子探针未与火焰接触;

燃烧器启动预吹扫及点离子探针与控制盒连线断开。火后燃烧器锁定离子探针电流太弱。(

燃气压力开关接近于实际燃气压力点火气量太小,或管道压力太低

燃烧器有预吹扫,无火焰燃气电磁阀损坏出现,燃烧器锁定点火棒安装错误或损坏

燃气管道内空气未清扫干净

模拟火焰存在(或炉内有火焰存在)

不能通过预吹扫,燃烧器

气体压力开关未调整好;风压太低;空气压力

锁定

开关损坏;燃烧头部损坏;燃烧头设置错误燃气压力开关设定值太高

温度控制开关接通,但燃燃气未供应烧器不启动燃气压力开关损坏或接触不好

风门执行器损坏

可能是燃气压力开关的设定值与实际压力太接近,当燃气阀门开启时,使管道燃气压力下

燃烧器连续循环执行吹

降,压力保护开关动作,燃烧器停机。当燃气

扫和点火但不锁定

电磁阀关闭后,管道压力上升,燃烧器又重新启动。排除方法是重新设定燃气压力开关值。

在检查以上情况后,如果故障依然存在,请检查电路的连接及各电插头是否连接好,包括风门伺服电机、燃烧器电机、气阀连线、点火变压器。如果燃烧器仍然不能工作,请与生产厂家联系。

运行失败

燃烧器进入锁定主要有如下原因:—火焰非正常熄灭

—离子探针接地不好—空气压力开关断开

如果燃气压力开关断开,则燃烧器会停机。

范文三:利雅路燃气燃烧器的调试与维护

利雅路燃气燃烧器的调试与维护

故障现象

故障原因

(1)气压不满足条件

1、接通电源,按启动、电机不转

(2)电磁阀不严,接头处漏气,检查锁定 (3)温控器开路

(4)条件回路至少有一个不成立(水位、压力、温度以及程控器是否通电起动) (1)燃烧器未接地

2、启动后前吹扫正常,(2)电磁阀不工作(主阀、点火阀) 但点不着火

(3)气压不稳定 (4)风量太大 (1)点火变压器烧坏

3、点不着火,气压正常,电有不打火

(2)高压线损坏或脱落

(3)间隙过大或过小,点火棒位置相对尺寸 (4)电极破裂或与地短路 (5)间距不合适

(1)气压不足,压降太大,供气流量偏小

4、点着后5ˋS后熄火 (2)风量太小,燃烧不充分,烟色较浓

(3)风量太大,出现白气 (1)风量太大

5、冒白烟

(2)空气湿度太大 (3)排烟温度较低 (1)环境温度较低 (2)小火燃烧过程较多

6、烟囱滴水

(3)燃气含氢量高,过氧量大生成水 (4)烟囱较长 (5)排烟温度较低 (1)没有电压 (3)马达失灵

7、燃烧器马达不转

(4)控制电路中断 (5)燃气输送中断 (6)接触器不动作 (7)热继电器损坏 (1)空气压力开关失灵

8、燃烧器马达运转,但(2)压力开关受污,管道阻塞 大约20秒后停机

(3)电磁阀不密封(只对带有密封检验装置的设备而言)

排除措施

(1)调整气压至规定值 (2)清理或修理电磁阀管道接头 (3)检查温控器是否闭合

(4)检查水位、压力、温度是否超限 (1)电路中接入地线 (2)换新

(3)调整气压至规定值 (4)减小配风,减小风门开度 (1)换新

(2)重新安装或换新 (3)重新调整 (4)重新安装或换新 (5)重新调整

(1)调整气压,清理滤网,增加到燃烧器需要流量

(2)重新调整风燃比 (3)重新调整风燃比 (1)调小风门

(2)适当减小风量,提高进风温度 (3)采取措施,提高排烟温度 (1)做好烟囱保温 (2)重新设定温控的设定值 (3)减小配风量 (4)降低烟囱高度 (5)提高炉温 (1)接上电路 (3)修理或更换

(4)寻找断开点,接触或断开调节器或监控器

(5)打开球阀,清理过滤器 (6)手动复位检验 (7)更换热继电器 (1)更换 (2)清洁

(3)排除不密封的情况

9、燃烧器马达运转,但在10秒后在预吹扫状态中停机

(1)压力开关触点没有接在运转位置(空气压力太小)

(2)鼓风机受污,热继动作 (3)燃烧器马达旋转方向错误

(1)正确调节压力开关,如果需要,进行更换 (2)清洁 (3)电源换相 (1)调节电极间距 (2)清洗

(3)排除接地,更换受损电极或电缆 (4)更换点火变压器

(1)更换电磁阀或排除电路不通的故障 (2)重新检查接地是否完好

10、燃烧器马达运转,(1)点火电极距离太大 电压加在点火变压器

(2)被污染 (4)点火变压器失灵

(1)电磁阀没有打开,因为电磁阀线圈损坏或电缆断裂 (2)接地线路断开

上,没有点火,稍后故(3)点火电极或电路接地 障停机

11、马达运转,点火正常,但稍后故障停机 12、在带有密封性检验

装置的设备中,燃烧器(1)电磁阀不密封 马达运转,点火正常,(2)供气不足 但稍后停机(无故障显(3)过滤器堵塞 示)

14、燃烧器马达运转,(1)电离电流不稳,太低 火焰形成正常,但随后(2)燃气空气混合调节不匀 故障停机

(3)点火火花影响到电离电流

(1)排除不密封的情况 (2)提高供气流量 (3)清洗或更换

(1)改变电离电极与火焰盘的位置,并检查连接线路 (2)重新调整燃气空气混合 (3)点火变压器初级线圈更换相线与中线

陕西东兴节能环保设备技术有限公司

2013年11月21日

范文四:利雅路燃气燃烧器RS5说明书

燃气燃烧器

GULLIVER RS5

代码 型号 类型

目 录

1..燃烧器总述------------------------------------------------------1 1.1燃烧器附件--------------------------------------------------1 2..技术数据---------------------------------------------------------2 2.1技术数据-----------------------------------------------------2 2.2总体尺寸-----------------------------------------------------2 2.3工作范围-----------------------------------------------------3 3..安装--------------------------------------------------------------4 3.1锅炉安装-----------------------------------------------------4 3.2燃气供给-----------------------------------------------------4 3.3燃气管路------------------------------------------------------5 3.4探针-电极位置---------------------------------------------------5 3.5电气连接-----------------------------------------------------6 4..工作--------------------------------------------------------------7 4.1燃烧调节-----------------------------------------------------7 4.2燃烧检查-----------------------------------------------8 4.3燃烧器启动程序-------------------------------------------------8 4.4空气压力开关-----------------------------------------------------9 5.维护---------------------------------------------------------------9 6.故障及解决办法-------------------------------------------------10

1 燃烧器描述

两段火燃气燃烧器 1 – 压力开关

2 – 连接阀门组的6孔插座 3 – 带7孔插座的控制盒 4 – 带锁定灯的复位按钮 5 – 燃烧头组装件 6 – 压力测点 7 – 带绝缘垫的法兰 8 – 风门调节组件 9 – 风门开启马达

◆ 燃烧器符合IP40,EN60529电保护等级 ◆ CE标志指90/396/EEC;PIN燃气使用标准

◆ 符合标准:EMC89/336/EEC,73/23/EEC,98/37/EEC,92/42/EEC. ◆ 阀门组符合EN676.

1.1 燃烧器附件

带绝热石棉垫的法兰 安装法兰用螺钉螺母 法兰用螺钉螺母

电容 7针插头

14111个 个 套 个 个

2 技术参数 2.1 技术参数

920 T1 类型

160-330kW - 137,600-283,800kcal/h 燃烧功率(1)

天然气 热值: 8-12kWh/m=7,000-10,340Kcal/m ( 2类 ) 压力: 最小20mbar—最大100mbar 电源 单相,230V±10% 50Hz

2A – 2750rpm – 289 rad/s 电机

8uF 电容

点火变压器 二级8Kv – 230V – 0.2A

0.43kW 用电总功率

(1)参考条件:温度:15℃ - 大气压 1013mbar – 海拔高度 0m

对于3类燃气(LPG)要应用备件:

国家

燃气种类

II2H3B/P

II2H3P

II2E3BII2H3BII2H3B/P /P /P

II2Er3II2H3P

P B,I3P

气 压

2.2 外观尺寸

2.3 燃烧范围

实验锅炉:以上工作曲线是用符合DIN 4788和EN 676标准的锅炉测量的。 商用锅炉:如果锅炉是符合EN303标准,且燃烧室尺寸与EN676图表所示相近时,则燃烧器与锅炉应该是匹配的。如果锅炉不是符合EN303标准或者燃烧室尺寸不符合EN676图表,请咨询生产厂家。

燃气压力与燃烧器出力的关系

在用热值为9.56kW/m3(8,230kcal/m3)的G20燃气、锅炉背压为0mbar时进行检测,燃烧器最大出力时燃烧器头部的压降为9.9mbar。

rabm

热功率

燃烧头处的气压值---mbar

热功率 热功率

炉膛背压

3安装

3.1 锅炉安装

如有必要,对石棉垫扩孔(3)。(请看图3) z 用螺钉(4)和螺母2)将法兰(5)安装到炉门(1)上,必须将石

棉垫(3)放在中间。注意保持上部两颗螺钉中的一颗松动.(见图2) z 将法兰5与燃烧头放好,用螺钉6紧固,拧紧松动的螺钉4.

注意:燃烧器具有可调的燃烧头长度(A,图4),总之,要保证燃烧头完全穿过锅炉前墙

.

z

3.2 供气

根据阀门组导线进入燃烧器的方向,确认保留电缆孔堵(1)和(2)(图5).

3. 3燃气供应管路

阀门组(依据EN 676)

阀门组 型号 代码 MBDLE 410 B01 3970549 MBDLE 412 B01 3970550 MBDLE 415 B01 3970558

1 – 供气管

2 – 手动球阀(安装者负责) 3 – 气压表(安装者负责) 4 – 滤网 5 – 压力表 6 – 安全阀 7 – 稳压器 8 – 调节阀

M1 – 供气压力测点 M2 – 阀门组后压力测点

接头

进口 Rp 1 1/4Rp 1 1/4Rp 1 1/2

出口 法兰 3 法兰 3 法兰 3

用法

天然气≤200kW 和 LPG 160 –330kW

天然气≤300kW 天然气≤300kW

阀门组单独供货,它的调整参考附带的说明书

3.4 探针—电极定位(图7)

注意:

确认固定板(1)总在电极的固定面

固定板 探针 将探针绝缘靠上内杯

3.5 电气连接

注意:

不应将零线与火线混淆连接 --- 导线直径1mm2。

--- 安装人员对电路的连接应符合当地的法规要求。 ★电容应连接于L1和7孔插座的N角,这一节点由燃烧器提供或由锅炉的7孔插座提供.

测试:

断开温度探头或将火焰探测电缆上的接头(C)断开,燃烧器应锁定并停机.

控制盒:

如要移去控制盒,在移去所有组件(包括7孔插座,连接头C,高张力电缆,地线(H))后松开螺钉(A,图8)

拆下控制盒时,用一1-1.2Nm的扳手将螺钉(A)再紧上.

C – 点火棒接头H – 接地螺钉h1 – 计时器

PA – 空气压力开关

PG – 最小燃气压力开关SB – 锁定灯(230V-0.5Amax)TR – 温度调节TS – 温度开关VS – 安全阀V1 – 调节阀

4.1燃烧调整(图9)

根据92/42/EEC标准在锅炉上使用燃烧器时,其调整和测试必须根据锅炉的使用说明书,这包括测量烟气中的CO和CO2的含量,温度和锅炉中的水温等

.

要保证燃烧器的出力,要选择燃烧头的正确设定和风门设定.

燃烧器出厂时在最小设定位.

燃烧头调节:

它取决于燃烧器的输出,拧动设定螺钉

(6)直到调节杆(2)上的刻度值与外端面(1)平齐的值是设定值.

在图9中的燃烧头的设定是燃烧器出力为230kW时.

可见燃烧头的设定值为4,即调节杆与外端面的对应值.

正常工作过程中,灭火后燃烧器在一秒内锁定;如燃烧器不能自启动,需要按一下复位按钮,之后燃烧器可以重新启动。

例如:

燃烧器安装在210kW锅炉上,其热效率为90%,燃烧器输出大约为230KW,按照以下图表,燃烧器燃烧头应设在4的位置。

此图表一般只在初期设定时参照,在运行时为了改变空气配比情况和燃烧状况,可适当更改此设置。 燃烧头组件的移开: 按下列顺序操作:

拧下螺钉(7),拆下连接(3)和(5),拆下外部小管(4),拧松螺钉(10),拿走燃烧头组件(1). 在拆卸时不要改变进气内管的设定. 安装燃烧头组件 注意:

■ 在安装燃烧头系统时,要将螺钉(7)拧上(不要拧紧),然后用一个3—4Nm的扳手拧紧.

■ 要保证在燃烧器工作时螺钉处不会有燃气泻漏.

■ 如压力测点(13)松动,应紧上并确证燃烧头组件(1)外部的孔(F)拧向低的部位.

风门调节(图9,页7)

在拧松螺母(9)后调节螺钉(8).

除了烟囱负压为0.5max,燃烧器停机时风门会自动关闭. 注意:在风门设定小于设定点1时不要点火.

4.2 燃烧检查

建议根据燃气种类和下表来设定燃烧器:

EN676 过量空气系数:最大输出λ≤1.2 – 最小输出λ≤1.3

CO Nox 天然气为理论设定CO2%

Mg/kWh Mg/kWh 值时的O2% λ=1.2 λ=1.3

≤100 ≤170 ≤100 ≤170 ≤100 ≤230 ≤100 ≤230

点火电流

燃烧器控制器所需最小电流为5μA。

一般情况下,离子探针电流会大于5μA。在需要检查时,可以打开离子探针红色连接头(C)(页6),串接入微安电流表。(图10)

接头C

控制盒接点

4.3 燃烧器启动图

正常

温度传感

风门马达 马达 点火变压器 阀门 火焰 锁定

火焰故障锁定

A 控制盒上的信号灯指示燃烧器锁定。

当燃烧器在运行时因火焰故障锁定时,会在1秒内停机。

4.4空气压力开关:

z 空气压力开关应在最后调节,开始时应设在最低位置。

z 燃烧器工作在最小出力时,顺时针加大设置值,直至燃烧

器锁定,然后将设定值逆时针旋转减小一格。

z 检查燃烧器是否能稳定工作,如果燃烧器突然停机,应再

减小空气压力开关的设定值。 注意:

作为标准条例,空气压力开关调整要防止当空气压力达到设定的80%时排烟中的一氧化碳超过1%(10,000ppm)。

若要检查这一条,请在烟囱中放入燃烧分析仪,缓慢关闭风机的进气口(例如用卡纸板)并且检查燃烧器在排烟中的一氧化碳含量超过1%之前是否会锁定。

5 维护

燃烧器要求定期维护,这样才能保证燃烧器工作的稳定,避免浪费燃料和造成污染.

基本的检查有:

让燃烧器连续运行10分钟,按说明书设定好各个部件,做燃烧检查: CO2的含量 CO的含量 烟温

11

6.故障现象及原因

下面是造成启动故障或燃烧器非正常运行等问题的原因及相应的解决办法。

故障通常会造成位于控制盒(3,图1,页1)复位键中的失火灯亮。

当失火灯亮时,只有按复位钮燃烧器才会重新启动,此后如果燃烧器运行正常,锁定可以归因于暂时故障。但是,如果继续锁定,一定要查找原因,并加以解决。

故障

当调节温度开关闭合时燃

烧器不启动

原因

没有电源 没有燃气

解决方法

检查L1-N夹上的电压

检查保险 检查温度开关TL 检查手动球阀开度 检查电磁阀已打开并无短

路 调整

检查并重连接

替换

检查电气连接

风门没全关所以燃烧器点火接触器不动:检查

重接 连接好

检查离子探针的位置 重新电气连接 更换损害的连接

燃气压力开关没闭合 控制盒中的连接错误 空气压力开关在运行位置

风门卡住

燃烧器预吹扫和点火正常,

过3秒后锁定

中火线混淆

地线没有或接触不好 离子探针接地不好;离子探针未与火焰接触;离子探针与控制盒连线断开;与地短

12

故障

燃烧器点火延迟

原因

点火电极位置不对

空气太多

阀门开太小,燃气量不够 电磁阀过气量很小 电磁阀损害 点火脉动或失败 管道没用空气吹扫

空气压力开关不切换 火焰熄灭

压力测点(11,图9,页7)位

置不对

解决方法

调整 重调 调整

检查管网压力/调整电磁阀

更换 检查接头 检查电极的位置 燃气管网吹扫干净

更换

空气压太低(燃烧头调节错

误)

阀门组坏:更换 调整好位置

减小最低燃气压力开关的工作压力。

燃烧器在预吹扫后因火焰

故障锁定

燃烧器在预吹扫时锁定

燃烧器不锁定,重复启动

主燃气压力接近于最低燃气压力开关所限定的数值。阀门开启跟随着不断的压力降低,从而引起压力开关自身的暂时开启,阀门立即关闭,燃烧器停机。压力又升高,压力开关再次关闭,重复点火周期。该过

程没有休止地进行。

运行中故障:

燃烧器锁定: -- 灭火

-- 探针接地

--空气压力开关断开

燃烧器停机: -- 燃气压力开关断开

13

范文五:利雅路燃气燃烧器FS20说明书

燃气燃烧器

RIELLO 40 FS20

TYPE 569T30 CODE 3756935

目 录

1. 技术参数--------------------------------------------------1 2. 结构说明--------------------------------------------------1 3. 配件------------------------------------------------------2 4. 燃烧器的安装----------------------------------------------2 5. 燃烧范围--------------------------------------------------2 6. 适用锅炉--------------------------------------------------2 7. 燃气压力与燃烧器出力的关系--------------------------------3 8. 燃气供应管路----------------------------------------------3 9. 电极位置--------------------------------------------------4 10. 电路连接图------------------------------------------------4 11. 燃烧器启动时序图------------------------------------------5 12. 风门调节--------------------------------------------------6 13. 燃烧器头调节----------------------------------------------6 14. 燃烧状况检查----------------------------------------------6 15. 离子探针电流----------------------------------------------7 16. 空气压力开关----------------------------------------------7

17. 燃烧器启动故障现象及其造成原因----------------------------8

1. 技术参数

燃烧功率 燃气要求 热值 (天然气) 压力

电源 电机 电容

点火变压器 用电总功率

z z z z z

81-232KW=70,000-200,000Kcal/h 8-12kWh/m=7,000-10,340Kcal/m

最小20mbar—最大35mbar 单相,220V±10%50Hz

230V/1.4A 5uF

一级230V/1.8A - 二级8kV30/mA

0.25kW

对液化石油气(或城市燃气)需要特别的部件。 CE标准,符合90/396/EEC;PIN63AP6680。 EMC符合89/336/EEC。

燃烧器符合IP40,EN60529保护标准。 燃气阀门组符合EN676标准。

2. 结构说明

1—风门 2—紧固螺钉 3—电缆垫圈 4—外壳紧固螺钉 5—6孔气路组件插座

6—7孔输入和远程控制插座 7—报警灯及复位按钮

注意:电缆垫圈(3)和外壳紧固螺钉(4)必须与阀门组在同一方向。

结构尺寸

* 可使用加长的燃烧头

1

3. 配件

数量 1 4 1 1 1 1

说明 七针插头 紧固螺钉及螺母 石棉垫片

外壳紧固螺钉 电缆垫圈 铰链

4. 燃烧器的安装

将燃烧器上部螺钉(1)打开,使图中(A)与(B)部分分开。

在燃烧器头部(B)安上石棉垫片(3)然后与锅炉(2)紧固连接。

5. 燃烧范围

6. 适用锅炉

z z

实验锅炉:以上工作曲线是用符合DIN 4788和EN 676标准的锅炉测量的。 商用锅炉:如果锅炉是符合EN303标准,且燃烧室尺寸与EN676图表所示相近时,则燃烧器与锅炉应该是匹配的。

z

如果锅炉不是符合EN303标准或者燃烧室尺寸不符合EN676图表,则燃烧器与锅炉是不匹配的。此时应咨询生产厂家。

2

7. 燃气压力与燃烧器出力的关系

在用热值为10kW/m3(8,570kcal/m3)的燃气、锅炉背压为0mbar时进行检测,燃烧器最大出力时燃烧器头部的压降为7.7mbar。

8. 燃气供应管路

1—燃气供应管道 2—手动阀 3—过滤器 4—调压阀

符合EN 676标准的气体阀门组:

DUNGS 气阀型号 MBDLE407B01MVDLE 207/5

连接尺寸 阀门组燃烧器

燃气条件

5—燃气压力测点 6—燃气压力开关 7—电磁阀

8—电磁阀出口燃气压力检测点

可更换的RIELLO气阀型

天然气≤180kW 1. DUNGS GF 507/1过滤器

液化石油气 2. DUNGS FRS 207/1调压器 天然气和液化石3. DUNGS GW 50A4压力开关

Rp3/4 Rp3/4

4. Riello 487SE和488SE燃气阀 油气

燃气控制阀门组的调节方法可参考有关资料。

3

4

安装、使用以及维护说明书

9. 电极位置

10. 电路连接图

5

注意

z z z z z

以上电路中不应将零线与火线混淆连接。 导线直径1mm2。 应有安全接地。

应确定燃烧器能在锅炉温度报警和火焰离子探针与燃烧器连线(红线)断开时,就停止工作。

安装人员对电路的连接应符合当地的法规要求。

11. 燃烧器启动时序图

6

正常工作过程中,灭火后燃烧器在一秒内锁定;如燃烧器不能自启动,需要按一下复位按钮,之后燃烧器可以重新启动。

12. 风门调节

z 风门(1)是由手动控制

z 拧松调节螺钉(4),将风门开度(3) 调到适当的开度。

z 当达到合适的风门开度时将螺钉4 拧紧。

z

出厂时,风门设置为3。

13.燃烧器头调节:

拧松螺钉A,移动弯管B到合适位置,再拧紧螺钉A。 例如:

燃烧器安装在155kW锅炉上,其热效率为90%,燃烧器输出大约为172KW,按照以下图表,燃烧器燃烧头应设在3的位置。

7

安装、使用以及维护说明书

此图表一般只在初期设定时参照,在运行时为了改变空气配比情况和燃烧状况,可适当更改此设置。

14.燃烧状况检查:

z z

CO2的含量应不超过10%,如果CO2含量太高,将会产生由于不完全燃烧或CO含量过高而引起的危险。

按照EN676标准,CO含量应不超过100mg/kWh(80ppm)

8

安装、使用以及维护说明书

15.离子探针电流:

燃烧器控制器所需最小电流为3μA。

一般情况下,离子探针电流会大于3μA。在需要检查时,可以打开离子探针红色连接头,串接入微安电流表。(如图所示)

16.空气压力开关:

z z

空气压力开关应在最后调节,开始时应设在最低位置。

燃烧器工作在最小出力时,顺时针

z

加大设置值,直至燃烧器锁定,然后将设定值逆时针旋转减小一格。 检查燃烧器是否能稳定工作,如果燃烧器突然停机,应再减小空气压力开关的设定值。

注意:

根据有关标准,如果CO含量超过1%(10000ppm),则必须调节空气量及空气压力开关。(应首先确定CO含量的增加是由于风量不够而引起的)

9

安装、使用以及维护说明书

17.控制盒的复位和故障诊断

控制盒有故障诊断功能在任何情况下方便故障的显示(指示器:红色 LED)。 为使用该功能,首先必须在燃烧器进入安全状态(锁定)10秒后,然后再按住复位按钮。

控制盒会产生一系列的脉冲闪烁(1秒间隔),在一个3秒的间断后重复出现。 此时计数脉冲闪烁的次数就可确定可能的故障原因,系统的复位必须按住复位按钮1至3秒。

.控制盒复位及故障诊断如下所示.

控制盒复位

控制盒复位时,按以下步骤进行:

-按复位按钮保持1-3秒. 松开按钮2秒后燃烧器会重新启动.如燃烧器不能启动,必须检查温控器接点是否闭合. 显示诊断

指示出燃烧器锁定的故障原因. 按以下步骤进行诊断:

-如LED红灯常亮,按住复位按钮保持3秒以上.黄灯闪后,松开复位按钮. 根据P11所示的故障表,闪烁的次数就代表各自的故障原因.

软件诊断

通过连接的PC机来监视燃烧器状态,可以指示运行时间锁定原因及控制盒序列号等...

按以下步骤进行诊断:

-如LED红灯常亮,按住复位按钮保持3秒以上.

松开按钮1秒,再按复位按钮3秒以上直到黄灯再闪..

再次松开按钮后,红灯高频闪烁:说明与计算机的连接已经接通. 做完诊断后,控制盒必须通过复位程序恢复到初始状态.

按按钮时间 按1-3秒 按住超过3秒

显示诊断后按住超过3秒

控制盒状态

控制盒复位,没有显示诊断.

锁定状态下的显示诊断: (LED 闪烁有1秒的间隔).

通过接口与PC机连接进行软件诊断 (运行时间, 故障等的监视)

10

信号

故障

可能原因 建议解决方法

闪两次 吹扫和安全时间

后燃烧器锁定并且没有火焰出现

闪三次 燃烧器不能启

动,锁定出现 燃烧器启动然后锁定

1-电磁阀VR只允许少量燃气进入 . . . . . . . 增大开度 2-电磁阀VR不能打开 . . . . . . .. 更换线圈或整流器面板3-燃气压力过低 . . . . . . .. 通过调压器增大燃气压力 4-点火电极调节不正确 . . . . . . .. . . . . 重新调节 5-点火电极由于绝缘破坏而接地 . . . . . .. . . 更换 6-高压电缆损坏 . . . . . . . . . . . . . . . . 更换 7-高压电缆由于高温变形 . . . . . . . . . 更换和保护 8-点火变压器损坏 . . . . . . . . . . . .. . . 更换 9-阀或点火变压器接线错误 . . . . . . . . . . . 检查 10-控制盒损坏 . . . . . . . . . . . . . . . . 更换 11-阀门组下行管道中的旋塞关闭 . . . . . . . . 打开 12-管道中有空气 . . . . . . . . . . .. .. . 排出空气 13-VR 没有连接上或线圈断开 . . . 检查连接或更换线圈 14-空气压力开关在运行位置调整或更换

空气压力开关由于空气流量不足而不起 作用:

15-空气压力开关调整不当 . . . . . . .. . 调整或更换 16-压力开关压力点管道阻塞 . . . . . . . . . . 清理 17-燃烧头调整不当 . . . . . . . . . . . . . . 调整 18-燃烧室背压过高 . . . . . . . . . . . . . . . . . . 将空气压力开关连接到风机空气入口

19-电容损坏 . . . . . . . . . . . 更换

20-马达损坏 . . . . . . . . . . . . . . . 更换 23-虚假火焰 . . . . . . . . . . . . . . 更换控制盒 24-燃烧室有火焰或有虚假火焰 . . 消除余火或更换控制盒 25-电磁阀VR只允许少量燃气通过 . . . . .. . 增加气量 26-离子探针调整不当 . . . . . . . . . . .. . . 调整 27-电离度不够 (小于5 μA) . . . . . .检查离子探针位置 28-离子探针接地 . . . . . . . . . . . 缩短或更换电缆 29-燃烧器接地不良 . . . . . . . . . . . . . 检查接地 30-火线与零线接反 . . . . . . . . . .. . . 重新连接 31-控制盒故障 . . . . . . . . . . . . . . . . 更换 33-离子探针或电缆接地 . . . . . . . . . . . . 更换 34-空气压力开关故障 . . . . . . . . . . . . . 更换

预吹扫时锁定

闪四次 燃烧器启动后锁

燃烧器停止时锁定

闪七次 火焰出现后燃烧

器马上锁定

运行时,燃烧器停机并锁定

11

闪十次 燃烧器不能启

动,锁定出现 燃烧器锁定 不闪

燃烧器不启动

35-错误的电气连接 . . . . . . . . . . . . 检查连接 36-控制盒故障 . . . . . . . . . . . .. . . . 更换 37-没有电源 . . . . . . . . 闭合所有开关,检查连接 38-温控器或安全控制装置断开 . . . . . . 调整或更换 39-控制盒保险熔断 . . . . . . . . . . . . 更换

40-控制盒锁定 . . . . . . . . . . . . . . . . 复位 41-没有燃气供应 . . . ... 打开仪表和管道之间的手动阀 42-主燃气压力不足 . . . . . . . . . 与燃气公司联系 43-最低燃气压力开关不能闭合 . . . . . 调整或更换 44-伺服马达无法运行到st1位置 . . . . . . . . 更换 45-主燃气压力接近于最低燃气压力开关所限定的数值. . . 减少最低燃气压力开关的工作压力

阀门开启跟随着不断的压力降低,从而引起压力开关更换燃气过滤器.自身的暂时开启,阀门立即关闭,燃烧器停机.压力又升高,压力开关再次关闭,重复点火周期.该过程 没有休止地进行.

46-燃烧头调整不当 . . . . . . . . . . . . 调整 47-点火电极调整不当 . . . . . . . .. . . . 调整 48-风机风门调整不当:风量过大 . . . . . . . 调整 49-点火阶段输出功率过高 . . . . . . . 减少输出功率

燃烧器重复启动周期,而不锁定

点火脉动

12

燃烧器启动故障现象及其造成原因

原 因

离子探针接地不好;离子探针未与火焰接触;

燃烧器启动预吹扫及点离子探针与控制盒连线断开。 火后燃烧器锁定 离子探针电流太弱。(

燃气压力开关接近于实际燃气压力 点火气量太小,或管道压力太低

燃烧器有预吹扫,无火焰燃气电磁阀损坏 出现,燃烧器锁定 点火棒安装错误或损坏

燃气管道内空气未清扫干净

模拟火焰存在(或炉内有火焰存在)

不能通过预吹扫,燃烧器

气体压力开关未调整好;风压太低;空气压力

锁定

开关损坏;燃烧头部损坏;燃烧头设置错误 燃气压力开关设定值太高

温度控制开关接通,但燃燃气未供应 烧器不启动 燃气压力开关损坏或接触不好

风门执行器损坏

可能是燃气压力开关的设定值与实际压力太接近,当燃气阀门开启时,使管道燃气压力下

燃烧器连续循环执行吹

降,压力保护开关动作,燃烧器停机。当燃气

扫和点火但不锁定

电磁阀关闭后,管道压力上升,燃烧器又重新启动。排除方法是重新设定燃气压力开关值。

在检查以上情况后,如果故障依然存在,请检查电路的连接及各电插头是否连接好,包括风门伺服电机、燃烧器电机、气阀连线、点火变压器。如果燃烧器仍然不能工作,请与生产厂家联系。

故 障

运行失败

燃烧器进入锁定主要有如下原因:—火焰非正常熄灭

—离子探针接地不好 —空气压力开关断开

如果燃气压力开关断开,则燃烧器会停机。

13

范文六:利雅路燃气燃烧器RS190M说明书下载

安装、使用以及维护说明

燃气燃烧器

RS190/M

中国燃烧机网www.ranshaoji.net

目录

技术参数--------------------------------------------------------------------------------------------------------------------1

附件-----------------------------------------------------------------------------------------------------------------1燃烧器描述-----------------------------------------------------------------------------------------------------------------2包装-重量-----------------------------------------------------------------------------------------------------------------2最大尺寸---------------------------------------------------------------------------------------------------------------------2标准附件---------------------------------------------------------------------------------------------------------------------2燃烧出力---------------------------------------------------------------------------------------------------------------------3测试锅炉---------------------------------------------------------------------------------------------------------------------3商用锅炉---------------------------------------------------------------------------------------------------------------------3燃气压力---------------------------------------------------------------------------------------------------------------------4安装---------------------------------------------------------------------------------------------------------------------------5锅炉板------------------------------------------------------------------------------------------------------------------------5燃烧头长度------------------------------------------------------------------------------------------------------------------5燃烧器固定到锅炉上------------------------------------------------------------------------------------------------------5设定燃烧头------------------------------------------------------------------------------------------------------------------6气体管线------------------------------------------------------------------------------------------------------------------------7电气系统--------------------------------------------------------------------------------------------------------------------8点火前调整------------------------------------------------------------------------------------------------------------------11伺服电机-----------------------------------------------------------------------------------------------------------------------11燃烧器起动-----------------------------------------------------------------------------------------------------------------11燃烧器点火-----------------------------------------------------------------------------------------------------------------11燃烧器校准-----------------------------------------------------------------------------------------------------------------121-点火输出功率----------------------------------------------------------------------------------------------------------122-最大输出功率-------------------------------------------------------------------------------------------------------123-最小输出功率------------------------------------------------------------------------------------------------------134-中间输出功率---------------------------------------------------------------------------------------------------------135-空气压力开关---------------------------------------------------------------------------------------------------------146-最高燃气压力开关--------------------------------------------------------------------------------------------------147-最低燃气压力开关--------------------------------------------------------------------------------------------------14火焰有无检查------------------------------------------------------------------------------------------------------------14燃烧器运行----------------------------------------------------------------------------------------------------------------15最终检查------------------------------------------------------------------------------------------------------------------16维护-------------------------------------------------------------------------------------------------------------------------16故障-可能的原因-排障建议-----------------------------------------------------------------------------------------18

本文中所提到的图形如下标识:

1)(A)=图A的第1部分,与文本同页1)(A)p.4=图A的第1部分,页号4

来自中国燃烧机网www.ranshaoji.net

1

技术数据

型号类型

第2级

输出功率(1)

第1级最小输出功率

kWMcal/hkWMcal/h

G20108.60.7123015

RS190/M836T11279~22901100~1970

470405

天然气:G20-G21-G22-G23-G25

KWh/Nm3Mcal/Nm3kg/Nm3Nm3/hmbar

G258.67.40.7826722

LOK16。

燃料净热值

绝对密度最大输气流量最大流量时的压力(2)

运行方式标准应用环境温度燃烧空气温度

电源

-间隙式(24小时最少停机一次)(每24小时至少停1次)如果此燃烧器配置LANDIS250A27(或LANDISLAL1.25)程序控制器,也可用于连续运行-滑动两级式或比例调节式(见附件)

oCoC

电动机启动电流控制盒点火变压器电功率消耗电力保护电磁相容性噪声级(3)

认可

最大值VHz

RpmWVAA

锅炉:水,蒸汽,导热油

0-4060

230~400带零线~+/-10%

50-三相28004500

220/240~380/415

15.8~9.1126~72.8LFL1.333

230V~1×8kV1A~20mA

5500IP44

90/396-89/336-73/23-92/42

83.10085AP0709

V1-V2

I1-I2Wmax

dBACE

1)2)3)参考条件:环境温度20℃,大气压力1000mbar,海拔100m

测试点8)(A)p.2处的压力,燃烧室压力为零,燃气环2)(B)p.6开启,燃烧器输出功率最大。

制造商燃烧实验室中所测得的噪音级,燃烧器运行在测试锅炉上,而且处于最大额定输出功率测定的。

附件:(可选)

�比例调节器:在比例调节方式运行下,燃烧器能根据负荷的变化自动在大、小火间进行调节,以保证所需的温度或压力.为使燃烧器能以比例调节方式运行,须用以下两配件:1安装于燃烧器的负荷调节器

2安装于锅炉的测量装置

�燃气管路参照EN676标准(包括阀门、压力调节器和过滤器)见第8页

来自中国燃烧机网www.ranshaoji.net

2

来自中国燃烧机网www.ranshaoji.net

3

来自中国燃烧机网www.ranshaoji.net

4

来自中国燃烧机网www.ranshaoji.net

5

来自中国燃烧机网www.ranshaoji.net

6

来自中国燃烧机网www.ranshaoji.net

7

来自中国燃烧机网www.ranshaoji.net

8

来自中国燃烧机网www.ranshaoji.net

9

来自中国燃烧机网www.ranshaoji.net

10

来自中国燃烧机网www.ranshaoji.net

11

来自中国燃烧机网www.ranshaoji.net

12

来自中国燃烧机网www.ranshaoji.net

13

来自中国燃烧机网www.ranshaoji.net

14

来自中国燃烧机网www.ranshaoji.net

15

来自中国燃烧机网www.ranshaoji.net

16

来自中国燃烧机网www.ranshaoji.net

17

来自中国燃烧机网www.ranshaoji.net

故障表

颜色

故障

1-2-3-4-5-6-7-8-9-10-11-可能原因

没有电源

限制器或安全控制装置打开控制盒锁定

控制盒保险丝熔断电气连接错误控制盒损坏没有燃气供应主燃气压力不足

最低燃气压力开关不能关闭空气压力开关没有闭合

伺服马达凸轮II无法运行,控制盒端子11-8

建议解决方法

闭合所有开关,检查连接调整或更换重置控制盒更换

检查连接更换

打开仪表和管道之间的手动阀与燃气公司联系调整或更换调整或更换

调整凸轮II或更换伺服马达更换控制盒更换

更换

所掉相重接上后,重置热继电器调整凸轮I或更换伺服马达调整或更换清洗调整更换控制盒

调整凸轮III或更换伺服马达增加燃气通过量

更换线圈或整流器面板增加控制器处的压力调整,参见图C)p.5更换更换

更换或保护更换检查更换打开

排出空气

增加燃气通过量调整,参见图C)p.5重新连接

燃烧器不启动◄

燃烧器不启动且有闭锁

燃烧器启动后锁定在最大风门燃烧器启动后马上锁定

燃烧器启动后马上锁定

燃烧器停在预吹扫阶段

12-出现模拟火焰

13-电动机远程控制开关损坏

(RS38-50/M)14-电动机损坏

15-)电机保护跳闸(RS38-50/M)16-伺服马达凸轮I无法运行,控制盒端

子9-8

空气压力不足,空气压力开关不工作17-空气压力开关调整不适当18-压力开关压力点管道阻塞19-燃烧头调整错误20-火焰检测循环故障

21-伺服马达凸轮III无法运行,控制盒

端子10-8

22-电磁阀VR只允许很少燃气通过23-电磁阀VR或VS不能打开24-燃气压力过低

25-点火电极调整不正确

26-电极由于绝缘破坏而接地27-高压电缆损坏

28-高压电缆由于高温而变形29-点火变压器损坏

30-阀或点火变压器接线错误31-控制盒损坏

32-阀门组下行管道中的旋塞关闭33-管道中有空气

34-电磁阀VR只允许很少燃气通过35-电离探针调整不正确36-探针的电接线故障

18

P

■▼

在燃烧器预吹扫和安全时间之后,燃烧器进入锁定状态,火焰不出现。1

火焰出现后燃烧器马上锁定

来自中国燃烧机网www.ranshaoji.net

来自中国燃烧机网www.ranshaoji.net

控制盒(1)装配有圆盘(2),它在启动阶段旋转并且可以从控制盒的下部观察得到。当燃烧器因为故障,不启动,或锁定时,与指针(3)所对应的颜色表示故障的种类。

来自中国燃烧机网www.ranshaoji.net

19

范文七:利雅路燃气燃烧器说明书

燃气燃烧器

GULLIVER BS3-4/M

目 录

1..燃烧器描述------------------------------------------------------1 1.1燃烧机附件--------------------------------------------------1 1. 2 燃烧机随机附件

2..技术资料---------------------------------------------------------2 2.1技术资料-----------------------------------------------------2 2外观尺寸-----------------------------------------------------2 2.3燃烧范围-----------------------------------------------------3

3..安装--------------------------------------------------------------4 3.1锅炉安装-----------------------------------------------------4 3.2瓦斯电磁阀-----------------------------------------------------4 3.3燃气供应管路------------------------------------------------------5 3.4探针-电极定位---------------------------------------------------5

4..线路图--------------------------------------------------------------7 4.1内部线路图-----------------------------------------------------7 4.2外部线路图-----------------------------------------------8

5..工作--------------------------------------------------------------7 5.1燃烧调整-----------------------------------------------------7 5.2燃烧头设定-----------------------------------------------8 5.3风门档板设定-------------------------------------------------8 5.4第一次激活-----------------------------------------------------9 5.5燃烧检查-----------------------------------------------------9 5.6空气压力开关-----------------------------------------------------9 5.7瓦斯压力开关-----------------------------------------------------9 5.8燃烧器激活图-----------------------------------------------------9

6.维护---------------------------------------------------------------9 7故障及解决办法-------------------------------------------------10

燃烧器描述 (图1)

燃烧器符合IP40,90/396/EEC; PIN 0085BN0609电保护等级 ◆ CE标志指90/396/EEC;PIN燃气使用标准

◆ 符合标准:EMC89/336/EEC,73/23/EEC,98/37/EEC,92/42/EEC. ◆ 阀门组符合EN676.

1 – 带绝热石棉垫的法兰 2 – 燃烧头 3 – 燃烧程控器 4 – 带锁定灯的覆归按钮 5 – 风门调节控制器 6 – 燃烧头设定螺丝 7 – 空气压力开关 8 – 燃烧室压力测点 (连接瓦斯电磁阀) 9 – 控制燃烧器双段/比例输出的 4孔插座 10 – 7孔插座(燃烧机供给) 11–电磁阀组的6孔插座 12 – 压力测点 (连接瓦斯电磁阀) 13 –手动或自动运转开关 (MAN / AUT), 增加或减少输出功率开关 (+/-)

2.1 燃烧器附件 带绝热石棉垫的法兰 安装法兰用螺钉螺母 法兰用螺钉螺母 蓝色塑料管

2.2 燃烧器选用配件(另购)

1411个 个 套 个 4孔插头 G1/8结合点 7孔插头 1个 1个 1个

3 技术资料

3.2外观尺寸

3.3燃烧范围

注 意 : 为使燃烧机有效地运用,激活时必须总是在有关的燃烧范围。

实验锅炉:以上工作曲线是用符合EN 676标准的锅炉测量的。

商用锅炉:如果锅炉是符合EN303标准,且燃烧室尺寸与EN676图表所示相近时,则燃烧器与锅炉应该是匹配的。如果锅炉不是符合EN303标准或者燃烧室尺寸不符合EN676图表,请咨询生产厂家。

燃气压力与燃烧器出力的关系

在用热值为9.45kW/m3(8,127kcal/m3)的G20燃气、锅炉背压为0mbar时进行检测,916M型燃烧器最大出力时燃烧器头部的压降为9.3mbar(M2,参见3.页8 )。

4. 安装

3.1 锅炉安装

 如有必要,对石棉垫扩孔(3)。(请看图3)  将燃烧机压力供应点(7)放入法兰(5)  用螺钉(4)和螺母2)将法兰(5)安装到炉门(1)上,必须将石棉垫(3)

放在中间。注意保持上部两颗螺钉中的一颗松动.(见图2)  将法兰5与燃烧头放好,用螺钉6紧固,拧紧松动的螺钉4.  检测压力供应点(7)确定能穿过衬垫,若讯号危弱时,直接将压力点安装至燃

烧室(若可能,请立即穿过检验窗管),若安装不正确,燃烧室之压力点太大,会造成燃烧不良或运转危险.

注意:燃烧器具有可调的燃烧头长度(A,图4),总之,要保证燃烧头完全穿过锅炉前墙

3.2 瓦斯电磁阀(根据 EN 676)

瓦斯电磁阀分开供应,安装及调整请参阅附属操作手册.

注意

˙ 锅炉接头A和连接电磁阀接头 Pf间的接管子须固定,可使杂物排进燃烧室而不会进入阀体 ˙ 导压用连接管必需简短

˙ 导压连接管不可接触到锅炉因高温会损坏它.

˙ 当燃烧室之压力若测量不正确,请将燃烧机法兰G1/8连接器移动至锅炉门,突出法兰孔 ˙ 错误之安装方法将造成阀门故障受损

4.3 燃气供应管路 图.7

4.线路图

4-1内部线路图

注意:

不要将空档的更换为阶段式 不应将零线与火线混淆连接 --- 导线直径 1mm2

--- 安装人员对电路的连接应符合当地的法规要求

6.燃烧机运行 6.1燃烧调整

根据92/42/EEC标准在锅炉上使用燃烧器时,其调整和测试必须根据锅炉的使用说明书,这包括测量烟气中的CO和CO2的含量,温度和锅炉中的水温等.

要保证燃烧器的出力,要选择燃烧头的正确设定和风门设定.燃烧器出厂时在最小设定位.

6.2燃烧头设定(图9):

它取决于燃烧器的输出,转动设定螺钉(6)直到调节杆(2)上的刻度值与外端面(1)平齐的值是设定值.在图9中的燃烧头的设定是燃烧器出力为230kW时.可见燃烧头的设定值为3.5,即调节杆与外端面的对应值.

例如:917M 此图表一般只在初期设定时参照,在运行时为了改变空气配比情况和燃烧状况,可适当更改此设置。

燃烧器安装在210kW锅炉上,其热效率为90%,燃烧器输出大约为230KW,按照以下图表,燃烧器燃烧头应设在3.5的位置。

燃烧头组件的移开: 按下列顺序操作

˙确定伺服马达(7)位于全关位置.

˙拧下螺钉(4),拆下连接(3)和(5),拿走燃烧头组件(7).在拆卸时不要改变进气管的设定. 注意:

˙旋转风门马达位(7)内之轴承,以起安全机械做作用(11),此可防止当维修进行时发生运转意外.

˙拧下螺钉(8), (9),轻轻地向右转动,拿走燃烧头组件(1).

˙当拆下时,不要改变轴型弯管(2)之设定安装燃烧头组件,反过来根据以上部骤,将燃烧头座(1)装回到原来之位置. 注意:

■ 在安装燃烧头系统时,要将螺钉(9)拧上

(不要拧紧),然后用一个3—4Nm的扳手拧紧

■ 要保证在燃烧器工作时螺丝钉处不会

有燃气泄漏.

■ 如图10,为使燃烧机运作超过所附之输出功率,于

917M,918M,必须移动空白处的隔音材料增大空气补充量,使成为一个空气孔进入燃烧机

图表 10

6.3风门挡板设定 (图11 )

 待机 : 凸轮II

风门角度全关位置,当燃烧机关掉时(待机).

原厂设定值在0

˚(不可改变)  小火 :凸轮III

设定点火位置及小火输出量的风门挡板角度, 凸轮III 同时控制凸轮IV.  大火 :凸轮I

设定大火输出量的风门挡板角度, 原厂设定值在90˚(设定值绝对不可超过90˚), 否则造成燃烧机损坏.

当凸轮III之角度减小时风门马达会随着凸轮位置作调整.若凸轮角度需要增加时,可以朝“增加输出功率+”方向增加伺服马达之角度, 如果凸轮角度需要减小时,可以朝“增加输出功率-”方向减小伺服马达之角度.

当需要调整凸轮位置时,可以移动外盖(1),盖子里面有调整工具(2),并将它插入凸轮缺口调整风门檔皮角度.

◆将值设定接近开始值之刻度(-1.5).

1. 以最大需求输出功率,设定燃烧头位置,设定值可以参考第10页的下方图表

2. 选择手动运转模式“MAN”并依据上列表格设定风门马达之凸轮III之角度,及调整归零点的设定值后,激活燃烧机.

3. 一旦点着火,用手按(+)键,移动风门马达向大火位置,运转期间,检测火焰是否稳定:若不稳定,增减调整瓦斯及空气的比例设定直到最大需求输出功率,并随时检测烟气中二氧化碳值. 然后设定最大输出功率凸轮I位置

4. 用手按(一)键,移动风门马达向小火位置,检测燃烧状况 5. 若小火输出功率需改变,只需调整凸轮III的角度

6. 再次将风门马达转至最大输出功率,并调整瓦斯空气比例设点.

7. 再次转动风门文件板至小火位置,并再次调整最大输出功率,并只用归零设点调整. 8. 重复步骤(6)和(7),直到瓦斯空气比例设点及归零设点不再需调整为止.

9. 检测燃烧值在中间输出功率并若于需要时,进一步地调整瓦斯空气比例设点及归零设点. 一旦完成并确定燃烧机火焰稳定外观良好,选择自动模式 “AUT”. 调节将影响凸轮III和凸轮I 之定位

6.5 燃烧检查

火焰电流

燃烧器控制器所需最小电流为2μA。 一般情况下,离子探针电流会大于5μA。在需要检查时,可以打开离子探针连接头(CN3)(页11),串接入微安电流表。(图13)

控制盒接點

接头CN3

电流微安表

火焰检知棒

6.6空气压力开关:

 空气压力开关应在最后调节,开始时应设在最低位置。

 燃烧器工作在最小出力时,顺时针加大设置值,直至燃烧器锁定,然后将设定值逆时针旋转

减小一格。

 检查燃烧器是否能稳定工作,如果燃烧器突然停机,应再减小空气压力开关的设定值。

注意:

作为标准条例,空气压力开关调整要防止当空气压力达到设定的80%时排烟中的一氧化碳超过1%(10,000ppm)。

若要检查这一条,请在烟囱中放入燃烧分析仪,缓慢关闭风机的进气口(例如用卡纸板)并且检查燃烧器在排烟中的一氧化碳含量超过1%之前是否会锁定。

6.7瓦斯压力开关:

瓦斯压力开关设定请参阅瓦斯电磁阀操作手册.

5.8燃烧器激活图

温度极限开关 安全温度开关

马达

伺服马达位置:2

(大火)

伺服马达位置:1(小火) 伺服马达位置:0(全关)

点火变压器 瓦斯电磁阀

大火 小火

燃烧器安装有电离光系统,它保证火焰的检测,如果燃烧器点火失败,在燃气电磁阀门开启的3秒内,燃烧器进入锁定状态,控制盒指示灯将红亮,如果运行中燃烧器火焰突然熄灭,则燃烧器将在1秒内锁定。

警告: 不要把火线和零线颠倒,如果接反了,会导致燃烧器因点火失败而锁定。

程控器:LMG22内部线路图

7. 维护

燃烧器要求定期维护,这样才能保证燃烧器工作的稳定,避免浪费燃料和造成污染. 基本的检查有:

让燃烧器连续运行10分钟,按说明书设定好各个部件,做燃烧检查: CO2的含量(百分比) CO的含量

烟囱温度 ( ˚C )

9.故障现象及原因

控制盒(1)装配有圆盘(2),它在激活阶段旋转并且可以从控制盒的下部观察得到。当燃烧器因为故障,不激活,或锁定时,与指针(3)所对应的颜色表示故障的种类。

范文八:利雅路燃烧器RS5

安装 , 使用及维护说明书

强制通风燃气燃烧器

一段火运行

编码

型号

类型

3761900 RS5 920 T1

2902967 (0)

目录

1. 2.

燃烧器描述 . . . 技术参数. . .

1 1 2 2 2 3 4 4 4 5 5 6

6.

故障 / 解决方法 . . .

10

5.

维护 . . .

9

1.1 燃烧器附件 . . . 2.1 技术参数. . . 2.2 外观尺寸. . . 2.3 工作范围. . . 3.

安装 . . . 3.1 锅炉安装. . .

3.2 燃气阀组电气连接 . . . 3.3 燃气管线. . . 3.4 电极定位. . . 3.5 电气连接. . .

4. 工作 . . .

4.1 燃烧调节 . . . 4.2 4.3 4.4 4.5

燃烧头设置 . . . 风门挡板设置 . . . 燃烧检查 . . .

燃烧器启动程序 . . .

7 7 7 8 8 9 9

4.6 空气压力开关 . . .

1. 燃烧器描述

一段火强制通风燃气燃烧器 . 燃烧器保护等级为 IP 40, EN 60529.

CE 认证 : 参照燃气应用标准 92/42/EEC; PIN 0085BM0114.

燃烧器符合下列标准 : EMC 89/336/EEC, 低电压 73/23/EEC, 机械 98/37/EEC 和效率 92/42/EEC. 燃气阀组符合 EN 676.

图 . 1

1 - 压力开关

2 - 燃气阀组 6 孔插座 3 - 带 7 孔插座的控制盒 4 - 带锁定指示灯的复位按钮 5 - 燃烧头安装座 6 - 压力测试点 7 - 带绝热垫的法兰 8 - 风门调整机构 9 - 风门伺服马达

SW1001

1.1 燃烧器附件

带绝热垫的法兰 . . . 法兰用螺栓螺母 . . . 马达启动电容 . . .

. 1 . 1 . 1

将法兰安装到锅炉上的螺栓和螺母 . . . 7 针插头 . . .

. .. 4 .1

2967

1 中

2. 技术参数

2.1 技术参数

类型

燃烧器出力 (1) 天然气 ( 品种 2) 电源 马达

马达启动电容 点火变压器 电功耗

920 T1

160 - 330 kW - 137,600 - 283,800 kcal/h

净热值 : 8 - 12 kWh/Nm3 = 7000 - 10,340 kcal/Nm3 压力 : min. 20 mbar - max. 100 mbar 单相 , 230 V ± 10% ~ 50Hz

运行电流 2 A - 2750 rpm - 289 rad/s 8 μF

初级 230 V / 0.2 A - 次级 8 kV / 12 mA 0.43 kW

(1) 参考条件 : 温度 . 20°C - 大气压力 1013 mbar - 海拔 0 m .

对燃用 LPG 可选特殊附件 .

国家 燃气种类

G20 H

燃气压力

G25 G20

L E

IT

GB

DE

AT

DK

FR

NL

BE

IE

II2H3B/P II2H3P II2E3B/P

20 - -

20 - -

- - 20

II2H3B/P II2H3B/P II2Er3P II2L3B/P I2E(R)B,I3P II2H3P

20 - -

20 - -

- - 20 / 25

- 25 -

- 25 20 / 25

20 - -

2.2 外观尺寸

503

278 − 300

300

225 − 203

150

150

218 137 170 200

216

D4476

2967

2 中

2.3 工作范围 ( 参照 EN 267)

4.0 3.2 2.4 1.6 0.8 0 150 130,000

170

190

210

230

250

270

290 250,000

310

330

350 kW

kcal/h

D6231

170,000 210,000 290,000

燃烧器出力

实验锅炉

以上工作曲线是用符合 EN 676 标准的锅炉测量得到 .

商用锅炉

如果锅炉是符合 EN 303 标准,且燃烧室尺寸与 EN 676 图表所示相近时,则燃烧器与锅炉是匹配的 . 如果锅炉不是符合 EN 303 标准,且燃烧室尺寸比 EN 676 图表所示更小 ,请咨询生产厂家 .

燃气压力与燃烧器出力的关系

在用热值为 10 kWh/m3 (8.570 kcal/m3) 的 G20 燃气和锅炉背压在 0 mbar 进行检测时,燃烧器最大出力时燃烧 器头部的压降为 9.9 mbar(M2, 参见 3.3, P. 5).

10 9 8 7 6 5 4 3 2 150 130,000

170 190 210 230 250 270 290 250,000

310 330 350 kW

kcal/h

D6232

170,000 210,000 290,000

燃烧器出力

2967

3 中

3. 安装

燃烧器的安装必须符合当地法规和标准 .

3.1 锅炉安装

♦ 如有必要 , 对绝热垫扩孔 (3) ( 参见图 . 3).

♦ 用 4 个螺钉 (4) 和螺母 (2) 将法兰 (5) 安装到炉门 (1) 上,必须将绝热垫 (3) 放在中间,但应保持上部两颗螺钉 中的一颗松动 (4) ( 参见图 . 2).

♦ 用螺钉 6 将法兰 5 固定到燃烧头上 紧固,拧紧松动的螺钉 4.

注意 .: 燃烧器具有可调的燃烧头长度 (A) ( 参见图 . 4). 总之 , 要保证燃烧头完全穿过锅炉前墙 .

图 . 2 图 . 3 D5012

A 225 - 203 图 . 4

SW1003

图 . 5

D6341

3.2 燃气阀组电气连接

燃气阀组连 接电线可从左边或右边进入燃烧器 ,如 图 5

2

所示 .

根据进入燃烧器的方向 , 带压力测试点的电缆孔堵 (1) 和 简易电缆孔堵 (2) 可能需要互换 .

因此 , 必须确认 :

电缆孔堵 (1) 位置正确 ;

气管位置应正确 , 以保证空气通畅 , 不会对空气压力开 关造成阻塞 . 注意

如有必要 , 可将气管切到正确的长度 .

1 2

D4605

1

2967

4 中

3.3 燃气管线

1 - 供气管

2 - 手动球阀 ( 安装者负责3 - 燃气压力表 ( 安装者负4 - 过滤器

5 - 燃气压力开关 6 - 安全阀 7 - 稳压器 8 - 调节阀

M1 - 供气压力测试点 M2 - 阀组后压力测试点 符合 EN 676 的燃气阀组

D5209

燃气阀组单独供货 , 它的调整参考附带的说明书 .

3.4 探针 - 点火电极定位 , ( 参见

图 . 7)

2967

D4020

固定板 探针

使探针绝缘体稍微倾斜靠着护罩

5

3.5 电气连接

230 V ~ 50 Hz

L

N

主开关

T6 A

不要将零线与火线接反 .

注意 :

- 最小电线截面积:1 mm . ( 除非有当地的法规和标准 ).

- 电线的连接必须符合所在国家的强制规定 .

电容应连接于 7 孔插座的 L1 和 N 端子 ,7 孔插座由燃烧器提供或由锅 炉提供 .

测试

断开温控器开关,检查燃烧器是否停机 ; 断开连接器

(C) 与控制盒的连接,检查燃烧器是否锁定 .

2

*

TS

电容

TL

*

7 针插头 L1 7 孔插座

控制

N T1 T2 S3 B4

S3

h1

控制盒

如要将控制盒从燃烧器上移去 , 移开所有组件后 , 7 针 插头 , 连接器 (C), 高张力电缆和 地线 (H) 拧松螺钉 (A, 图 . 8).

在拆下控制盒后,用螺丝刀(1 - 1.2 Nm)紧上螺钉 (A).

PA

569

兰色

黑色 白色 兰色

马达

风门伺服马达

M

~

M

电容

黑色

褐色

C

H

D6234

燃烧器接地

6 孔插座 3 2 1 6 针插头 3 2 1

N Ph

N Ph

C H

- 离子探针连接插头 - 接地螺钉

图 . 8

S7003

h1 - 计时器

PA - 空气压力开关

气压力开关 PG - 最小燃

S3 - 远传锁定信号 (230V - 0.5 A max.)

PG

TL - 启动温控器 V10 - 安全阀 V11 - 调节阀

V11 V10

TS - 安全温控器

2967

6 中

4. 工作

燃烧出力

燃烧器点火应在低负荷状态下进行并不超过 120 kW.

为了测量燃烧出力 :

- 断开离子探针电缆上的连接插头 (C) (参见电气连 接P. 6); 燃烧器点火并在安全时间 (3s)过后锁定 . - 进行 10 次点火并连续锁定 .

- 从流量表中读出耗气量 . 该耗气量应等于或小于 以下数值 :

G20 ( 天然气 H) 为 0.10 Nm

3

G25 ( 天然气 L) 为 0.10 Nm

3

G31 (LPG) 为 0.03 Nm.

3

4.1 燃烧调整 ( 参见图 . 9)

根据燃烧器应用于锅炉上的效率标准 92/42/EEC, 调试燃烧器必须参考锅炉的使用说明书 , 这一工作 包括调整烟气中的 CO 和 CO2 含量,烟温及锅炉中 的平均水温 .

要达到所需要的出力 , 要选择正确的燃烧头设定值 和风门设定值 .

燃烧器出厂时设定在最小出力 .

4.2 燃烧头设定

根据燃烧器的出力 , 通过顺时针和逆时针旋转 设定 螺丝 (6) 来进行 , 直到标尺 (2) 上的刻度值与燃烧头 座 (1) 的外边缘对齐 .

在图 9 中的燃烧头的设定是对应于燃烧器出力为 230 kW.

可见燃烧头的设定值为 4, 即 标尺上的刻度值与燃 烧头座的外边缘对齐 .

示例 :

燃烧器安装在 210 kW 的锅炉 .

考虑到锅炉效率为 90%, 燃烧器出力应为 230 kW. 如图所示 , 燃烧头应设在 刻度 4.

图 . 9

SW1004

kcal /h kW

350

290,000 270,000 250,000 230,000 210,000 190,000

330 310 290 270 250 230 210 190 170 150

注意

此图表仅供参考 ; 为了获得较好的燃烧170,000 效果 , 建议 可根据锅炉调整燃烧头的设定 .

150,000 130,000

2 4 6 8 10

2967

D6235

设定点

7 中

范文九:利雅路燃烧器gas3

htpt://wekn.uabdi.cuom/ivw/eace9337f311f11883d055a27ht.lm

htt

:p//enwuk.baiu.comd/veiw/9ac3e373f11f118583d5072.athml

ht

p:/t/wenk.uaidub.ocmv/ew/i9ca3e37311ff185813d5a72.ht0l

mht

pt/:/wnkue.biaud.cmo/vew/ia9ec337311ff11883d055a7.2htlm

h

tt:p/w/nkue.aidu.cbm/vioe/w9aec3373f111f18853d0a75.h2mlt

thp:t//ewkun.aidbuc.omvi/we9/ae3c37f3111f8583d15072a.thlm

tht://wenkpubai.d.uomcvi/we9/ca33e73f11f11588d3057a.htm2

lhttp://enwk.buidu.acom/viwe9a/ce333f1171f85813d05a7.h2mlt

http:/

/wnku.eaibd.uco/vmiw/e9aec333f711f1858130d5a2.7tmh

l

thtp:/w/nke.buida.uom/cveiw/ac9e33371f1118f53d805a72.hml

t

thtp//:wneuk.bidau.cmovie//w9cea3337f11f11883505da7.2tmhl

thpt://wekn.uaidubc.o/miev/9wca3337f1e1f1858130da527h.mlt

h

ttp://wneu.kabiduco./vmei/w9cea333f711118583fd50a7.h2mt

l

h

tp:/tw/nke.buiad.comu/ive/9waec333f117f11853d80a52.h7tlm

h

ttp/:/ewkn.baiduucom./vewi9ac/e333f117f18153d085a7.h2mtl

http:

//ewknub.iaducom/v.eiw9/cea33731f1f11883d055a2.h7ml

t

ttph://wnek.ubadi.uco/vimw/ea9e33c7f311f11583d850a27.thlm

htp:t/wenku./bidua.comvi/we9a/e3337fc11f11853805da2.html7

htp:/twenku.b/adiu.ocmv/ei/w9ace333f711f115883d50a7.htm2l

ttp:h//enwuk.aidu.cobmv/iew/ac9e333f11711f85380d57a2html.

htp://twekunba.diu.cmov/ie/9wae3c337f11f1158830d57a.2html

范文十:燃气燃烧器

燃气燃烧器(燃气燃烧机)故障原因分析及如何排除

在发生故障时,首先应从影响正常运转的主要问题开始,着手检查:

1. 是否有电? 2. 供气网的燃气压力是否正常,球阀是否打开?

3. 所有的调节装置如室温和锅炉温度调节器、水量控制器、空气和燃气压力开关等,是否正确调节?

4. 燃烧时空气量和燃气流量是否有改变?

如果故障确非上述原因,则须去掉联锁,接通燃烧机,对有关功能进行测试。

燃气燃烧器(燃气燃烧机)安全控制要求

我国天然气和煤制气(原料为煤)资源丰富,且属于洁净能源,顾有着良好的社会经济效益。燃气燃烧机符合我国产业政策,市场前景很好,大有发展前途。然而在燃气燃烧机研制设计中,燃气特性—易燃、易爆及毒性,安全控制的首要问题。下面介绍一下燃气燃烧机的安全控制要求: 根据燃气在炉膛内的燃烧特性,对其安全控制要求内容主要有预吹风、自动点火、燃烧状态监控、点不着火的保护、熄火的保护、燃气压力高低限保护、空气压力不足保护、断电保护、预防燃气泄漏事故的措施等。

1.预吹风 燃烧机在点火前,必须有一段时间的预吹风,把炉膛与烟道中余气吹除或稀释。因为燃烧机工作炉膛内不可避免地有余留的燃气,若未进行预吹风而点火,有发生爆炸的危险.必须把余气吹除干净或稀释,保证燃气浓度不在爆炸极限内。 预吹风时间与炉膛结构及吹风量有关一般设置为15-60秒

2.自动点火 燃气燃烧机宜采用电火花点火,便于实现自动控制。可用高压点火变压器产生电弧点火,要求其输出能量为:电压≥3. 5K V、电流≥15mA , 点火时间一般为:2~5秒。

3.燃烧状态监控 燃烧状态必须予以动态监控,一旦火焰探测器感测到熄火信号,必须在极短时间内反馈到燃烧机,燃烧机随即进人保护状态,同时切断燃气供给。 火焰探测器要能正常感测火焰信号,既不要敏感,也不要迟钝。因为敏感,燃烧状态如有波动易产生误动作而迟钝,反馈火焰信号滞后,不利于安全运行。 一般要求从熄火到火焰探测器发出熄火信号的响应时间不超过0.2秒。

4.点不着火的保护 燃烧机点火时,通入燃气,燃气着火燃烧。点火动作要求发生在燃气通入前,先形成点火温度场,便于着火燃烧。如果点不着火,火焰探测器感测不到火焰信号,燃烧机进入保护状态。 从点火到进入保护状态的时间要适当,既不能过短也不能过长。若过短,来不及形成稳定火焰;过长,点不着火时造成大量燃气时入炉膛。一般要求在通入燃气2-3秒,燃烧机对火焰探测器感测的火焰信号进行判断,未着火则进入保护状态,着火则维持燃烧。

5.熄火保护 燃烧机在燃烧过程中,若意外熄火,燃烧机进入保护状态。由于炉膛是炽热的.燃气进入易发生爆燃,故须在极短时间内进入保护状态,切断燃气供给。 从发生熄火到燃烧机进人保护状态,该过程的响应时间要求不超过1秒。

6.燃气压力高低限保护 燃气燃烧机稳定燃烧有一定范围,只允许燃气压力在一定范围内波动。限定燃气高低压的目的是确保火焰稳定性:不脱火、不熄火也不回火,同时限定燃烧机的输出热功率,保证设备

安全经济运行。当燃气压力超出此范围,应锁定燃烧机工作。 燃烧机设计一般用气体压力开关感测压力信号,并输出开关量信号,用以控制燃烧机的相应工作。

7.空气压力不足保护 燃气燃烧机设计热强度大,其燃烧方式采用鼓风强制式。如果风机发生故障造成空气中断或空气不足,立即切断燃气,否则会发生炉膛爆燃或向风机回火。因此在提高风机质量的同时,燃气控制必须与空气压力连锁,当空气压力不足时,应立即切断燃气供给。 一般用气体压力开关感测空气压力信号,并输出开关量信号,用以控制燃气电磁阀的相应工作。

8.断电保护 燃烧机在工作过程中突然断电,必须立即切断然气供给,保护设备安全。燃气控制电磁阀必须是常闭型的,一旦断电,自动关闭切断燃气供给。电磁阀关闭响应时间≤5s.

9.预防燃气泄漏事故的措施 燃气泄漏包括二个方面,一指燃气通过管路向环境泄漏,二指燃气通过电磁阀阀芯端面向炉内泄漏。 环境泄漏可能引起人员中毒、工作现场爆炸事故,必须高度重视。首先确保管路密封,定期对管路检漏,若管路泄漏须排除方可继续使用;其次,避免造成中毒与爆炸的燃气浓度,要求工作现场通风良好:配置永久性的通风孔和强制通风装置;另外,要求工作现场禁止烟火、电气件防爆。 炉内泄漏可能引起炉内爆炸。解决炉内泄漏问题有三个途径:一是加强预吹风时间和吹风量,吹除或稀释炉内燃气;二是燃气管路采用二个电磁阀串联结构,提高系统安全性;三是使用管路泄漏检测装置,在点火前对燃气管路进行检测,若燃气泄漏达到一定量即锁定燃烧机工作。 预防燃气泄漏措施属外围控制,一般不纳入燃烧机本体控制。

燃气燃烧器的知识

气体燃烧器 气体燃烧器种类较多 , 以下按空气供给方式介绍几种工业锅炉上应用较多的燃烧器。

1. 自然供风燃烧器 如图 3-45 所示 , 按炉膛形状可以选择圆形或矩形燃烧器 , 低压燃气通过管子上的火孔流出 , 与空气事先元预混合 , 是一次空气系数α l=0 的扩散燃烧方式 , 因而也称为扩散文 燃烧器。这种燃烧器燃烧稳定 , 运行方便 , 而且结构简单 , 可以 利用 300~400Pa 的低压燃气。但炉膛过量空气系数较大 , α= 、 1.2~1.6; 排烟热损失 q2 和气体不完全燃烧热损失 q3 偏大 ; 火焰较长 , 要求炉膛容积大 ; 燃烧速度低 , 只用于很小容量的锅炉。

2. 引射式燃烧器 它的种类繁多。按燃烧方式分 , 它有部分空气预混合的本生燃烧方式和空气预混合的无焰燃烧方式两种。所用的引射介质可以是空气 , 也可以是一定压力的燃气 , 前者需要鼓风装置。

(1) 大气式引射燃烧器 如图 3-46 所示。燃气以一定流速自喷嘴进入引射器 , 在引射器的缩口处将一次空气 ( α1=0.45~0.65) 引入 , 两者经混合 后流向燃烧器头部 , 由直径为 2~10mm 的火孔流出 , 以本生 火焰形式燃烧。这种燃烧器也只用于小型锅炉 , 它适用于各种 低压燃气 , 而且不需要鼓风装置。但热负荷太大 , 结构笨重。

(2) 空气引射式燃烧器如图 3-47 所示。压头为 5000~600OPa 的空气经喷嘴通过引射器的缩口处时 , 形成负压 , 把低压的燃气从四个管孔 吸人 , 两种气体在混合管中混合形成均匀的气体混合物 ,

它 流向火孔出口 , 并在与出口处相连接的稳焰火道中燃烧。图中所示的燃烧器是与全部燃烧空气预混合的无焰燃烧器 , 炉 膛出口过量空气系数小 , 燃烧强度高 , 但需要鼓风装置 , 耗电大 , 适用于带有空气预热器的阻力较大的正压锅炉。

3. 鼓风式燃烧器 鼓风式燃烧器一般由分配器、燃气分流器和火道组成。种类较多 , 常用的有旋流式和平流式两种。 这两类燃烧器的配风器与燃油燃烧器基本相似 , 燃气分 流器的基本形式为单管式和多管式。其结构简单。燃烧形成的火焰特征与通常旋流式和直流式燃油燃烧器也相似 , 这里 不再一一叙述。以下列举一种常用的燃气燃烧器的例子。图 3-48 是周边供气蜗壳式燃烧器。从图中可知 , 空气通过蜗壳产生强烈旋转 , 后进入内筒 继续旋转向前 , 燃气由管子进入内环套 , 从内筒中部和端部 的两排小孔喷出、并与高速喷人的空气流强烈混合后进入火 道燃烧。在内筒的进口处的圆周上均布着一排曲边矩形孔 , 一小部分空气从这些小孔通过进入外环套, 作为二次空气在内筒端部环缝流出 , 它有冷却燃烧器头部的作用。这种燃烧器 混合强烈 , 燃烧完善 , 过量空气系数小 ( α=1 · 05), 但阻力较大。

4. 进口燃气燃烧器 图 3-49为进口燃气燃烧器构造图。主要由三部分组成 ,即气系统、风系统和控制系统 o 气系统功能是提供燃烧需要的燃气。主要由过滤器、稳 压器、压力开关、安全阀、电磁阀、流量调节阀、分配器等组成。 风系统的功能是提供燃烧所需要的一定数量和压力的空气。 : 主要由机壳、风机叶轮、风门、稳焰器 ( 配风盘 ) 、燃烧头、轴、滑杆、风门刻度盘、测压孔、燃烧头调整螺丝等组 成。控制系统的功能使燃烧器按规定的程序工作。主要由接线端子、穿线孔、控制盒、接触器、热继电器、点火变压器、点火电极、电机 ( 含伺服电机 ) 、光电管 ( 火焰传感器 ) 等组成。

控制系统的功能使燃烧器按规定的程序工作。主要由接线端子、穿线孔、控制盒、接触器、热继电器、点火变压器、点火电极、电机( 含伺服电机 ) 、光电管、 ( 火焰传感器 ) 等 组成。

燃烧器结构简要介绍

燃烧器结构 燃烧器作为一种自动化程度较高的机电一体化设备,从其实现的功能可分为五大系统:送风系统、点火系统、监测系统、燃料系统、电控系统。

1、送风系统 送风系统的功能在于向燃烧室里送入一定风速和风量的空气,其主要部件有:壳体、风机马达、风机叶轮、风枪火管、风门控制器、风门档板、扩散盘。

2、点火系统 点火系统的功能在于点燃空气与燃料的混合物,其主要部件有:点火变压器、点火电极、电火高压电缆。

3、监测系统 监测系统的功能在于保证燃烧器安全的运行,其主要部件有火焰监测器、压力监测器、监测温度器等。

4、燃料系统 燃料系统的功能在于保证燃烧器燃烧所需的燃料。燃油燃烧器的燃料系统主要有:油管及接头、油泵、电磁阀、喷嘴、重油预热器。燃气燃烧器主要有过滤器、调压器、电磁阀组、点火电磁阀组。

5、电控系统 电控系统是以上各系统的指挥中心和联络中心,主要控制元件为程控器,针对不同的燃烧器配有不同的程控器,常见的程控器有:LFL系列、LAL系列、LOA系列、LGB系列,其主要区别为各个程序步骤的时间不同。